Permit Number: T15CM00996
Parcel: 121110210

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM00996
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
03/04/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/04/2016 LOREN MAKUS ENGINEERING REVIEW Needs Review
03/04/2016 STEVE SHIELDS ZONING REVIEW Needs Review
03/05/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/05/2015 MARTIN BROWN FIRE REVIEW Approved
04/01/2016 KROBLES1 LANDSCAPE REVIEW Needs Review
07/14/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide,
A. Complete panel schedules, include load calc's for all phases and total load.
B. Service riser conductors undersized, See 310.15 75c table NEC.
C. Complete light fixture schedule.
D. Compliance with IECC for interior lighting.
E. Full compliance with the Tucson Outdoor Lighting Code.
F. One line diagram to include all fuse sizes and types, disconnect amp rating, voltage, phase.
G. Locate all loadcenters on the plan.
F. How are you going to re-feed panel 'A'.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2016 ARUIZ1 OUT TO CUSTOMER Completed