Permit Number: T15CM00971
Parcel: 111062800

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T15CM00971
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2016 KROBLES1 NPPO REVIEW Needs Review
01/22/2016 KROBLES1 ENGINEERING REVIEW Needs Review
01/22/2016 KROBLES1 BUILDING-RESIDENTIAL REVIEW Needs Review
07/16/2015 DAVID RIVERA ZONING REVIEW Denied P&DS TRANSMITTAL


FROM: David Rivera, Principal Planner
TRANSMITTAL: July 16, 2015
ADDRESS: 3402 E Monte Vista Drive
ACTIVITY NO: T15CM00971
PROJECT: Living space and storage room addition


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9 & .10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

COMMENT: The owner has constructed an addition along the east side yard with a building setback that is 4'-4" at the north end and 3'-8" at the south end of the addition. The overall height of the wall along the east side yard is 13'-8". The required building setback should be a minimum of 9'-2". A DDO is required for the existing building setback as noted above.