Permit Number: T15CM00968
Parcel: 10503034G

Address:
5151 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00968
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2015 STEVE SHIELDS ZONING REVIEW Approved
02/13/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the HVAC and ventilation for the two restrooms. The drawing shows no supply air being delivered to either restroom but the ventilation calculation shows 150 CFM being delivered to one restroom but the other restroom is not included in the calculation.
02/13/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/13/2015 ROBERT SHERRY WATER REVIEW Completed
02/13/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET C1: PLEASE PROVIDE A CODE ANALYSIS ON THIS SHEET PER THE IBC SECTION 107 REQUIREMENTS.
2. SHEET A1; FLOOR PLAN: THE PLAN INDICATES AN OFFICE/STORAGE AREA (863 SF) USING 100SF/OCCUPANT. HOW IS THE ACCESSIBILITY TO BOTH RESTROOMS AND AN EXIT DOOR ORIENTED SO STORAGE DOES NOT INTERFERE? PROVIDE GREATER DETAIL ON THE EXTENT OF THE STORAGE AREA, HOW IT WORKS WITH THE RESTROOMS AND EXIT, AND VERIFY THE OCCUPANCY LOAD.
3. SHEET A1; FLOOR PLAN: THE SINK IN THE BREAK ROOM CAN NOT SERVE AS AN ACCESSIBLE DRINKING FOUNTAIN OR SINGLE POINT-OF-USE WATER DISPENSER. PLEASE PROVIDE A NEW HIGH/LOW DRINKING FOUNTAIN OR A SINGLE POINT-OF-USE WATER DISPENSER ON THE DRAWINGS PER THE ICC/ANSI SECTION 602.
4. SHEET A1; FLOOR PLAN: NOTE 16 INDICATES AN EXISTING SERVICE SINK, BUT IS DEPICTED ON THE PLAN AS A LAVATORY. PLEASE CLARIFY.
5. SHEET A1; FLOOR PLAN: BOTH RESTROOMS MUST BE ACCESSIBLE PER THE IBC SECTION 3411. PLEASE REVISE.
6. SHEET A2; FRAMING PLAN: TWO LOCATIONS (AT THE BEAM TO POST NOTE) INDICATE TO SEE X/XX. PLEASE FINISH THE REFERENCE.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/13/2015 RSHERRY1 WWM REVIEW Passed No water meter size change.
02/13/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide drinking fountains.
2. Show how tempered water is to be provided for the two lavatories.
02/13/2015 JASON GREEN ENGINEERING REVIEW Approved
02/13/2015 MARTIN BROWN FIRE REVIEW Approved
02/13/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed