Permit Number: T15CM00967
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM00967
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/03/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the installation of the proposed inline fan with the electrical engineer (i.e. no power has been supplied to the fan). [Initial comment: Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012.]
03/03/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The proposed mixing valve is an obsolete product and is no longer being manufactured (it is also not lead-free). The product was listed to ASSE 1070 but the specification on sheet P100 incorrectly calls for a mixing valve that is listed to ASSE 1016. [Initial comment: Is the existing water heater being replaced? If so, show the installation of an ASSE 1070-listed mixing valve for the lavatory.]

Final Status

Task End Date Reviewer's Name Type of Review Description
03/17/2015 AROMERO4 OUT TO CUSTOMER Completed