Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/03/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/03/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Coordinate the installation of the proposed inline fan with the electrical engineer (i.e. no power has been supplied to the fan). [Initial comment: Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012.] |
03/03/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The proposed mixing valve is an obsolete product and is no longer being manufactured (it is also not lead-free). The product was listed to ASSE 1070 but the specification on sheet P100 incorrectly calls for a mixing valve that is listed to ASSE 1016. [Initial comment: Is the existing water heater being replaced? If so, show the installation of an ASSE 1070-listed mixing valve for the lavatory.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/17/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |