Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00871
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/11/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/24/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | SHEET A0 1. Please explain how Table 1018.1 with 50 occupants and no sprinklers allows for non rated corridors. SHEET A3.1 2. Door 108A is non compliant with 2012 IBC, Section 1005.7.1. A door swining into the egress corridior may not reduce the means of egress by more than 1/2 through out the entire swing. SHEET A3.3 3. At detail "A": The 5'-0" turn around space is cutting it too close with in the depth of the sink. Please provide detail of the actual sink showing knee space clearance at the point indicated on the plan and compliance with 2009 ICC A117.1, Section 306.3 (a). END OF REVIEW |
| 03/02/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/02/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the below-deck mixing valves specified for the lavatories located in restrooms conform to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 2. Water supply connections to beverage dispensers (e.g. coffee makers) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012. 3. Verify the location of the proposed indirect waste receptor in room 121 (Meds Room) is visible for inspection and has ready access for cleaning. Reference: Section 802.3, IPC 2012. |
| 03/02/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2012. 2. Skylights being replaced shall comply with the U-value and SHGC requirements for this climate zone per Table C402.3, IECC 2012. The product ratings shall have been determined to comply with NFRC Standard 100 by an accredited 3rd party testing laboratory. Reference: Section 303.1.3, IECC 2012. 3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. |
| 03/06/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |