Permit Number: T15CM00830
Parcel: 110113620

Address:
4755 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00830
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2015 DAVID RIVERA ZONING REVIEW Approved
02/09/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted during occupied hours. Reference: Section 403.2.1 (4), IMC 2012.
3. Revise the font size used on sheet M3 to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
02/09/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied Font size Plan Sheet E.4 cannot be less than 3/32" .This includes lower case.
02/09/2015 ROBERT SHERRY WATER REVIEW Completed
02/09/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/09/2015 RSHERRY1 WWM REVIEW Passed No water meter size change.
02/09/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an approved vacuum relief valve on the cold water supply for the water heater. Reference: Sections 303.2 and 502.1, IPC 2012.
2. Tempered water for the lavatories is required in the restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
3. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
02/09/2015 LOREN MAKUS ENGINEERING REVIEW Approved
02/09/2015 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/30/2015 KROBLES1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/30/2015 KROBLES1 OUT TO CUSTOMER Completed