Permit Number: T15CM00710
Parcel: 113094040

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM00710
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM00710
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. All SFR and Duplex plans submitted after March 1, 2009 require a solar water system, or future installation preparation City of Tucson Ordinance #10549 with one of the following provisions: ½"control conduit and two ¾" copper piping for water with rooftop termination; straight 3" capped sleeve; or an accessible attic (clear path 30" wide x 30" high) over the water heater. Show appropriate notation.
2. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 with the following provisions: 1. A 4 square feet area for (meter, disconnect & inverter) equipment adjacent to the electrical service panel or near the proposed collector panel space. 2. The best roof space available for accommodating PV solar collector panels with capacity for collector dead loading (typically 4 lbs/SF). 3. A minimum 3,800 volt-ampere PV electrical load entry on the Service Load Calculation (Show as a continuous load of 15.8 A). 4. An Electrical Panel Schedule with a 240 volt circuit breaker space labeled "reserved for Photo Voltaic". See electrical comments.
3. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. Property with 200 to 400 SF of available distribution area requires piping for one gray water fixture, and a property with over 400 SF requires complete compliance. Include two clothes washer standpipes, one with an above grade stub-out, and one to the building drain; also provide gray drain-line discharge of all second story bathing fixtures through an exterior-wall drop for future gravity distribution. Include an aliened purple colored 2" vertical drop to a cleanout cap 2' above grade. The home owner may perform system alteration for future gray water usage.

FOUNDATION PLANS:

1. Show compliance with termite treatment, R318.2.
2. Notate the grade away from foundations with a minimum 6" fall within the first 10', R401.3.

FLOOR PLANS:

1. Show the location of all patio cover support columns with dimensions, R106.1.1. Include the front porch roof that appears on the elevations and cross section A.
2. Show the door from a garage to dwelling with a 20-minute fire rating (or 1-3/8" solid core) with self-closing and self-latching provision, R302.5.1.
3. Show the garage floor direction of slope, R309.1.
4. Garages beneath habitable rooms require separation from all overhead habitable rooms by not less than 5/8" type X gypsum board or equivalent. Also, ½" GWB is required on supporting walls, R309.2.
5. Specify stair rise and run (min. 10" tread depth, 7 ¾" max. riser height, R311.7.5) and handrail height (R311.7.8.1).

STRUCTURAL PLANS:

1. Show a Garage door beam size with appropriate load carrying capacity for floor and roof above, R301.1.
2. Provide a header schedule and show existing opening sizes supporting new roof consistent with Table 502.5(1).
3. Provide a complete braced wall design, R602.10, or simplified design, R602.12. This design does not have a "qualifying" braced wall panel on the north wall ending at the east wall (Master bedroom at SGD).
4. Show any alternate braced wall panel hold-downs with appropriate tie-down capacity dependent upon wall height, Table R602.10.6.1.
5. Show garage opening narrow panels with fastening details using a prescriptive method at Figure R602.10.6.2, R602.10.6.3 or R602.10.6.4.

SECTIONS - DETAILS:

1. Specify anchor-bolt length for assuring 7" embedment into concrete or masonry, R403.1.6.
2. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.
3. Provide an attic space ventilation calculation and specify size and location of all vents needed to comply with R806.2

PLUMBING PLANS:

1. Show hot water pipe with minimum R-3 insulation, N1103.4.2.
2. Provide a water hammer arrester for quick-closing valves serving the clothes washer, P2903.5.
3. Provide a revised water fixture unit schedule using 2012 code values for verifying the required service pipe diameter, Table P2903.6. Those shown are not consistent with current codes.
4. Show a vent for the kitchen sink, P3114.
5. Show a provision for solar water preparation in compliance with City of Tucson Ordinance #10549 .
6. The revised City of Tucson Ordinance #11089 for gray water preparation requires separate second floor black and gray vertical drains to the below grade horizontal drain. Show the gray vertical drain for bathing fixtures at an exterior wall with purple stub-outs for future wye fitting alteration. Each second floor bathroom group may connect to an individual gray vertical drain.
7. Show or notate two clothes washer standpipes. Provide one discharge opening plumbed through an exterior wall with an above grade stub-out for gray water surface distribution. Provide a second discharge opening plumbed to the building black line in compliance with the City of Tucson Ordinance #11089.

MECHANICAL PLANS:

1. Provide (an HVAC system with) whole-house mechanical ventilation with continuous or a minimum controlled intermittent airflow rate, R303.4 & M1507.3. Show a source of outside supply air, or controlled exhaust fan.
2. Show supply ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, N1103.2.1. All other ducts outside of the thermal envelope require R-6 insulation. Update the ductwork notation.
3. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D.
4. Show dryer vent size and location for venting to exterior, M1501.
5. Clarify the exhaust fan CFM ratings shown differently on notation and schedule, R303.3 and M1507.3.

ELECTRICAL PLANS:

1. Show current code references, 2012 IRC. Update the Riser Diagram notation.
2. Revise the electrical load calculation showing a minimum 3,800 volt-ampere or 16 A continuous load entry for future Photo Voltaic equipment.
3.
4. Show a smoke alarm on each story of the dwelling, R314.3.3. Add detector at first floor.
5.
6. Island or peninsular counter tops require at least one receptacle outlet within 12" below the countertop surface, E3901.4.2 and E3901.4.3.
7. Show the location of all disconnect switches for air handling equipment, E4101.5.
8. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Adjustable security light fixtures are unshielded, not FCO.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 (R-30 with conditions) and walls R=13. Show the maximum "U" factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.25, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/27/2015 KROBLES1 OUT TO CUSTOMER Completed