Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00692
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/02/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/02/2015 | AROMERO4 | WWM | REVIEW | Completed | |
| 02/02/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 02/03/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1. Please include conductor sizes and types for new meter, service disconnect, and new panel. Plan Sheet E2. #2. Please identify in detail new and exsisting equipment on service one line diagram. Include elevator equip. #3. Emergency egress lighting required per TFD review. |
| 02/03/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/03/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 02/03/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/04/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012. |
| 02/04/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/04/2015 | ROBERT SHERRY | WATER | REVIEW | Completed |