Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T15CM00677
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/02/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
| 02/11/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide the following information per COT plan submittal requirements: #1. Feeder loads. #2 Rating and types of fuses and ckt. breakers. #3.Complete fault current analysis. #4.Complete panel schedules. Per NEC 110.3, IBC 107.2.1 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/30/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |