Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T15CM00676
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/02/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
02/02/2015 | JASON GREEN | ENGINEERING | REVIEW | Passed | |
02/11/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide the following information per COT plan check requiremments: #1. Feeder loads. #2.Rating and type of fuses , circuit breakers. #3. Complete fault current analysis. #4. Complete panel schedules. Per Nec 110.3 , IBC 107.2.1 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/30/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |