Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00660
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/30/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PROVIDE A VALUATION FOR THIS PROJECT. 2. PROVIDE STRUCTURAL CALCULATIONS FOR THIS PROJECT. 3. PROVIDE SPECIAL INSPECTION FORM. |
01/30/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
01/30/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/03/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
02/03/2015 | AROMERO4 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
02/03/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
02/03/2015 | AROMERO4 | ZONING | REVIEW | Needs Review | |
02/03/2015 | AROMERO4 | WWM | REVIEW | Completed | |
02/03/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the termination points for the sump pumps to discharge to the stormwater drain system. Reference: Section 1101.3, IPC 2012. |
02/03/2015 | AROMERO4 | FIRE | REVIEW | Needs Review |