Permit Number: T15CM00652
Parcel: 11008008C

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM00652
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2015 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 5-7-15
Activity: T15CM00652
Address: 2732 N. Orchard Ave
Applicant: Bill Clark

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code and local amendments. In order to facilitate a shorter back check time, we request that you provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide a minimum one-hour fire-rated wall assembly for all structures located within 36 inches of the fire separation line and subsequent fire-rated assemblies for projections attached to such structures, R302.1 as amended. Note: open-framed carport and porch structures must include a fire-rated wall that meets the above criteria. The note provided under the framing note section on sheet number 3 does not satisfy these requirements.

STRUCTURAL / FRAMING PLAN:
2. Provide roof framing members capable of supporting the imposed loads, R801.2.
Reference:
2x8 rafters at carport area are not rated to span 18 feet when spaced 24 inches on center
2x4 rafters at garage/storage area are not rated to span 14.5 feet at 16 inch centers
2x10 beam at garage area is not rated to support the proposed load at the span indicated
4x8 beam at carport area is not rated to support the proposed load at the span indicated
2x4 beam at porch area is not rated to support the proposed load at the span indicated

If you have any questions please contact: