Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2015 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 4-09-15
Activity: T15CM00651 2nd review
Address: 245 S 4th Av
Applicant: Rick Stertz

PREVIOUS COMMENTS:
1. Specify the size of all headers and beams including those located on the exterior porches and above the garage door, Table 502.5(1).
2. Specify the method of connection as well as the size and quantity of fasteners that will secure each roof ledger to the supporting wall, R801.2.
3. Provide a complete braced wall line layout showing the location of braced wall panels within 10 feet of each end of each braced wall line and shall be no more than 20 feet apart, R403.1.6, R602.10.2.2.
4. Indicate water supply line diameters and source of domestic hot water, P2901.1. Impact protection required for appliances located in garages.
5. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.
6. Provide location of return air ducts and register sizes, M1602. Minimum duct/register size: heat pump or air conditioner - 6 sq. in. / 1000 BTU, M1403.1 (1 ton cooling = 12,000 BTU).
7. Show dryer vent size and location for venting to exterior, M1502.
8. Designate the circuit number for each light fixture, receptacle, appliance, and equip disconnect on the electrical layout, E3703.5.
9. Show GFCI protection for all receptacles located in the garage (including ceiling mounted) E3902.
10. Specify feeder conductor and conduit sizes between the service panels, E3705.5.
11. Provide a receptacle to serve the clothes washing machine. Laundry rooms require a 20-amp circuit that shall serve no other outlets, E3703.3, 3901.8.
12. Specify tamper resistant receptacles per E4002.14.
13. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Model plans should specify a minimum lot size for the proposed exterior lighting.
14. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style) 104.2.
15. Specify the "R" value of the insulation, as well as the "U" factor and the solar heat gain coefficient of the windows and doors. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.40, SHGC=0.25, ceiling R=38 and walls R=13. Mass wall requirement is R=4 when 50% of insulation is exterior and R=6 when applied interior, N1102.1.
16. Condensation control is required for the unvented roof assembly method. Specify an air-impermeable rigid insulation material sealed tight to the roof sheathing or spray applied closed cell foam to a minimum value of R5, R806.5.

A review meeting may be scheduled with the plan reviewer specified below at your convenience if any of these items are unclear. A meeting must be scheduled with the designer and the property owner if these items are not addressed on the next submittal.