Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T15CM00644
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/06/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 02/18/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET MS1; GENERAL NOTES: THE CURRENT CODE ENFORCED BY THE CITY OF TUCSON IS THE 2012 EDITION OF THE IBC. PLEASE REVISE THE DRAWING. 2. SHEET MS1; GENERAL NOTES: THE CITY OF TUCSON HAS APPROVED AN ADDITION TO THE 2012 IBC. SECTION 1609.5.1.1 HAS BEEN ADDED FOR DESIGN-BASED WIND UPLIFT CRITERIA TO RESIST MICROBURST EFFECTS. THE DESIGN WIND VALUE OF 115 MPH SHALL BE USED FOR THAT APPLICATION. THIS VALUE EXCEEDS THE WIND LOAD USED IN THE CALCULATIONS. PLEASE VERIFY THE ANALYSIS. 3. SHEET MS1; GENERAL NOTES: A NOTE INDICATES THE LIGHT POLE FOUNDATION IS EXISTING. WAS THIS FOUNDATION DESIGNED FOR A POLE OF THE SAME PHYSICAL SIZE AS THE NEW POLE? IS THERE A COPY OF THE FOUNDATION DESIGN FOR THE PREVIOUS POLE AVAILABLE FOR REVIEW? PLEASE VERIFY. 4. STRUCTURAL CALCULATIONS; PAGE 1 (WIND DESIGN PARAMETERS): PLEASE REVISE THE CODES TO THE 2012 IBC AND ASCE 7-10. REVIEW THE CALCULATIONS TO INSURE THE NEW CODE REQUIREMENTS ARE SATISFIED. 5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/23/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide grounding details and wiring methods from origin of circuit to connection at light pole. Per NEC art. 300, 110.3, IBC 107.2.1. Compliance for Tucson Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/31/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |