Permit Number: T15CM00638
Parcel: 110120010

Address:
5330 E GLENN ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM00638
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2015 KEN BROUILLETTE FIRE REVIEW Passed TFD NOT THE AHJ
02/17/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S1; GENERAL STRUCTURAL NOTES: THE CITY OF TUCSON HAS APPROVED AN ADDITION TO THE 2012 IBC. SECTION 1609.5.1.1 HAS BEEN ADDED FOR DESIGN-BASED WIND UPLIFT CRITERIA TO RESIST MICROBURST EFFECTS. THE DESIGN WIND VALUE OF 115 MPH SHALL BE USED FOR THAT APPLICATION. THIS VALUE EXCEEDS THE 105 MPH LOAD USED IN THE CALCULATIONS PER THE ASCE 7-10. PLEASE VERIFY THE ANALYSIS.
2. SHEET S1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): PLEASE ADD VERBIAGE ON THE DRAWINGS FOR THE ALLOWABLE END BEARING CAPACITY OF 5000 PSF AND AN ALLOWABLE UNIT SKIN FRICTION OF 325 PSF FOR DRILLED PIER FOOTINGS PER THE GEOTECHNICAL EVALUATION.
3. SHEET S2; DETAIL 09: NOTE 9 WAS NOT LOCATED ON THE DETAIL. PLEASE VERIFY.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/23/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2015 AROMERO4 OUT TO CUSTOMER Completed