Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T15CM00638
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/06/2015 | KEN BROUILLETTE | FIRE | REVIEW | Passed | TFD NOT THE AHJ |
| 02/17/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET S1; GENERAL STRUCTURAL NOTES: THE CITY OF TUCSON HAS APPROVED AN ADDITION TO THE 2012 IBC. SECTION 1609.5.1.1 HAS BEEN ADDED FOR DESIGN-BASED WIND UPLIFT CRITERIA TO RESIST MICROBURST EFFECTS. THE DESIGN WIND VALUE OF 115 MPH SHALL BE USED FOR THAT APPLICATION. THIS VALUE EXCEEDS THE 105 MPH LOAD USED IN THE CALCULATIONS PER THE ASCE 7-10. PLEASE VERIFY THE ANALYSIS. 2. SHEET S1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): PLEASE ADD VERBIAGE ON THE DRAWINGS FOR THE ALLOWABLE END BEARING CAPACITY OF 5000 PSF AND AN ALLOWABLE UNIT SKIN FRICTION OF 325 PSF FOR DRILLED PIER FOOTINGS PER THE GEOTECHNICAL EVALUATION. 3. SHEET S2; DETAIL 09: NOTE 9 WAS NOT LOCATED ON THE DETAIL. PLEASE VERIFY. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/23/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/26/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |