Permit Number: T15CM00620
Parcel: 117024070

Address:
904 N PERRY AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM00620
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2015 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 2-23-15
Activity: T15CM00620
Address: 904 N. Perry Av
Applicant: Moses Thompson

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code and local amendments. In order to facilitate a shorter back check time, we request that you provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
1. Clarify location of braced wall panels indicated over window openings, R403.1.6, R602.10.2.2.
2. Specify series of I-joists at floor framing. Note: TJI 110 series are insufficient for the proposed design, R802.1.
3. Indicate the proposed stair riser dimension (max 7¾"), R311.7.

PLUMBING PLAN:
4. Provide vent sizes for the lavatory and shower or comply with wet-venting provisions, P3106.1 or P3108.
5. Specify the size of the proposed water meter and the diameter of the water supply line from the meter to the service entrance and the lowest available pressure, P2903.7. The Tucson Water policy adopted 7/13/12 limits the maximum demand for a 5/8" water meter to 15 GPM; Reference Tables P2903.6 and P2903.6 (1), IRC 2012.
6. Provide a water fixture unit schedule for all plumbing fixtures supplied by the water meter (including existing) P2903.6.
7. Clarify the location of the proposed water manifold in relation to the plumbing fixtures and the diameter of the fixture supply lines.

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/02/2015 AROMERO4 OUT TO CUSTOMER Completed