03/23/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM00603 R1
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

ELEVATIONS:

1. Provide consistent information for the vented attic space, R806. The current design does not show a 1" air space between the insulation and roof sheathing or sufficient eave vent opening. The first design did not show a condensation control provision with an air-impermeable rigid insulation material tight to the roof sheathing with a minimum R-5 value.
2. Provide an attic space ventilation calculation and specify size and location of all vents needed to comply with R806.2 if using a vented attic design. Provide appropriate upper and lower space vents if applying the reduced area calculation per exception requirements. Consider placement of insulation at the ceiling rather than the roof with added roof ventilators.
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5.

ELECTRICAL PLANS:

1. Clarify if the 200AMP service panel is existing or upgraded, E3702.2.
2. Revise the electrical load calculation following Table E3602.2 showing each appliance including the water heater.
3. Provide an appropriate circuit size for the water heater, E3702.5.
4. Protect all interior 15A & 20A proposed outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12. Update the panel schedule note since not all breakers are to be arc-fault circuit interrupters.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review