Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM00578
Parcel: 12701003R

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM00578
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET TS.1; GENERAL NOTES (10): REMOVE THE INTERNATIONAL RESIDENTIAL CODE FROM THE LIST.
2. GENERAL: PROVIDE A SITE PLAN PER THE IBC SECTION 107.2.5.
3. SHEET D.1; DEMO PLAN KEYNOTES: NOTES 1 AND 16 WERE NOT LOCATED ON THE PLAN. PLEASE VERIFY.
4. GENERAL: PLEASE PROVIDE A FLOOR PLAN INDICATING THE MEANS OF EGRESS PER THE IBC SECTION 107.2.3, INCLUDING THE NUMBER OF OCCUPANTS TO BE ACCOMMODATED AT EACH MEANS OF EGRESS.
5. GENERAL: PLEASE INDICATE ON THE DRAWINGS HOW THE MAXIMUM 20% OF THE TOTAL COST OF THE ALTERATIONS ARE APPLIED IN THIS PROJECT PER THE IBC SECTION 3411.7.
6. GENERAL: THE IBC SECTION 3411.6 INDICATES A FACILITY THAT IS ALTERED SHALL COMPLY WITH THE APPLICABLE PROVISIONS IN CHAPTER 11 (ACCESSIBILITY) UNLESS TECHNICALLY INFEASIBLE. THE IBC SECTION 1108.2.9 EXPLICITLY STATES THAT 'IN DINING AND DRINKING AREAS, ALL INTERIOR AND EXTERIOR FLOOR AREAS SHALL BE ACCESSIBLE', WITH A FEW EXCEPTIONS. PLEASE VERIFY THE DRAWINGS MEET THOSE SECTION REQUIREMENTS.
7. SHEET A.1; FLOOR PLAN: PLEASE VERIFY THAT THE EXISTING RAMPS IN THE DINING AREA MEET THE REQUIREMENTS OF THE IBC SECTION 1010. INDICATE THE ACTUAL RAMP SLOPE ON THE DRAWINGS IN KEYNOTE 19.
8. SHEET A.1; FLOOR PLAN: THE TWO RAMPS INTO ROOM 103 AND THE WEST RAMP INTO ROOM 104 APPEAR TO BE POTENTIAL TRIP HAZARDS. THE LANDINGS AT THE TOP AND BOTTOM OF THE RAMPS MUST MEET THE REQUIREMENTS LISTED IN THE IBC SECTION 1010.7. IT APPEARS THOSE CRITERIA ARE NOT MET. PLEASE REVIEW.
9. SHEET A.1; FLOOR PLAN: THE WALLS INDICATED AS TYPE 6A AT THE ENTRY (TWO THUS) AND THE WALL TYPE 6A AT THE DINING AREA ALL INDICATE 6" WOOD STUDS. THE WALL AT THE DINING AREA GRAPHICALLY APPEARS TO BE TWICE AS THICK AS THE ENTRY WALLS. PLEASE PROVIDE THE DIFFERENCE IN CONSTRUCTION OF THOSE WALLS ON THE PLANS, OR REVISE THE PLAN.
10. SHEET A.1; PARTITION TYPES: PARTITION TYPE 4B REFERENCES DETAIL 2/A.1. SHOULD THIS REFERENCE BE 3/A.1? PLEASE VERIFY.
11. SHEET A.1; FLOOR PLAN KEYNOTES: NOTES 1, 2, 13, 21, AND 25 WERE NOT LOCATED ON THE PLAN. PLEASE VERIFY.
12. SHEET A1.1; FLOOR PLAN: PLEASE INDICATE ON THE PLAN THE LOCATION OF THE ACCESSIBLE SEATING, INSURING THE REQUIREMENTS OF THE IBC SECTION 1109.11 ARE MET.
13. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/18/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the installation detail for the proposed water heater referenced on sheet P2.1. Provide the dimensions (diameter, offsets, and total height) of the existing flue to be used with the proposed water heater. Reference: Sections 303.2, 501.5, 503, 504, 606.1, 607.2, and 607.3, IPC 2012 and Section 107.2.1, IBC 2012.
2. Include all fixtures (i.e. include the existing fixtures) when calculating the total demand and determining pipe sizes. Note that when using the IAPMO fixture units, the water closets and urinals are to use "Assembly" fixture units. Reference: Section 604.3, IPC 2012.
3. Coordinate the total number of water fixture units in the plumbing fixture schedule with the water fixture units used in the pressure loss calculations. Verify the demand figure shown in the pressure loss calculations; the system is primarily a flush-valve system. Reference: Section 107.2.1, IBC 2012.
02/19/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the insulation for the new exterior walls complies with the minimum requirements detailed in Table C402.2, IECC 2012.
2. Provide structural calculations and details to show that the Type I hoods are supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.
3. Show that the hood installation complies with Section 507.9, IMC 2012 with regard to non-combustible supports, gypsum board, and with a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall, and extending 18" beyond the hood.
4. Correct keynote 22 on sheet M.2 for hood type and the location of additional information.
02/23/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2015 AROMERO4 OUT TO CUSTOMER Completed