Permit Number: T15CM00541
Parcel: 13615378C

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T15CM00541
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2015 MARTIN BROWN FIRE REVIEW Approved
01/29/2015 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Dairy Queen - 7825 E. Golf Links Road
T14CM00541
Building Plan (1st Review)

TRANSMITTAL DATE: January 29, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans appear to meet the proposed development package but Zoning cannot approve until a development package has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/29/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET T1
1. Code Review:
a. Item 3: Add occupancy group A2 to explanation
b. Item 4: Add 650 s.f. of Canopies
c. Correct governing accessibility code to 2012 Chapter 11 and 2009 ICC A117.1
d. Item 5: Add the patio occupancy to the occupancy load summary
SHEET S1.1
2. Provide certification for special inspectors.
END OF REVIEW
01/30/2015 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/10/2015 ROBERT SHERRY WATER REVIEW Completed
02/11/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The 2012 International Mechanical Code with Local Amendments is the relevant code for this project (see Mechanical Notes, sheet M.1)
2. Coordinate the component descriptions in the COMcheck envelope compliance certificate with the building plans (e.g. there is no continuous insulation on the roof and the walls are shown with R-19 insulation on the drawings).
3. Revise the mechanical design to comply with the requirements of Section C406, IECC 2012.
4. Clarify the efficiency of the proposed water heater; the energy factor (EF, test procedure DOE 10 CFR part 430) is expressed as a decimal, not as a whole number. Reference: Table C404.2, IECC 2012.
5. Provide calculations demonstrating adequate ventilation using the current code, the 2012 IMC. Reference: Section 403.2, IMC 2012.
6. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.
02/11/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the water demand calculation using the fixture unit values for public fixtures, not private fixtures. Hose bibbs have a continuous demand and are to be assigned a GPM demand and added to the demand determined for the plumbing fixtures. Reference: Sections E102.1 and E103.3 (2.1), IPC 2012.
2. Water supply connections to beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.
3. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
4. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
5. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
6. The minimum capacity for a hydromechanical grease interceptor shall be 25 GPM and 50-pounds of grease storage. Provide a specification for the hydromechanical grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
7. Show that the water-cooled equipment complies with Section 929, IMC 2012, as amended by the City of Tucson for water conservation.
02/18/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1 .Please show full compliance with the Tucson Outdoor Lighting Code.

#2. Please provide a complete Fault Current Analysis, (plan sheet E.3). Also note #3 references 2005 NEC , the 2011 is currently in use.( Plan sheet T1) refers to 2010 NEC.

#3. Please provide for GFI protected receptacles within 6' of outside edge of all sinks and in food prep areas, as per NEC 210.8 .
02/23/2015 JASON GREEN ENGINEERING REVIEW Reqs Change ENG can not approve the building plan until approval of the DP Package, DP14-0227. Once the DP is approved ENG will stamp the building plan approved at the counter.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2015 CPIERCE1 REJECT SHELF Completed