Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00489
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/10/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
02/19/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | SG-1 1. At the code analysis data chart: a. Clarify the type of construction from I1 to IA. b. Provide the occupant load SHEET A-1 2. Please identify existing and new building elements. 3. Correct square footage area to 4,800 s.f. as shown on SG-1, Code Analysis Data chart. 4. Correct occupant load from 8 to 10. SHEET A-3 5. If the toilet room is existing, why is this sheet submitted? END OF REVIEW |
02/26/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
02/26/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
02/26/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Keynote 17 on sheet A-4 refers to "thru-wall heat pump and air conditioner units"; are these new or existing, and where are they located? |
03/03/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/09/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |