Permit Number: T15CM00489
Parcel: 10610001E

Address:
1825 W PRICE ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00489
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2015 MARTIN BROWN FIRE REVIEW Approved
02/19/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SG-1
1. At the code analysis data chart:
a. Clarify the type of construction from I1 to IA.
b. Provide the occupant load
SHEET A-1
2. Please identify existing and new building elements.
3. Correct square footage area to 4,800 s.f. as shown on SG-1, Code Analysis Data chart.
4. Correct occupant load from 8 to 10.
SHEET A-3
5. If the toilet room is existing, why is this sheet submitted?
END OF REVIEW
02/26/2015 ROBERT SHERRY WATER REVIEW Completed
02/26/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/26/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Keynote 17 on sheet A-4 refers to "thru-wall heat pump and air conditioner units"; are these new or existing, and where are they located?
03/03/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2015 KROBLES1 OUT TO CUSTOMER Completed