Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM00488
Parcel: 13323099L

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM00488
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET 1.1; BULDING PLAN: INDICATE ON THE PLAN THAT THE PLATFORM IS TO BE REMOVED.
2. SHEET 1.1; BUILDING PLAN: INDICATE ON THE PLAN THE EXIT SIGNAGE AS REQUIRED BY THE IBC SECTION 1011, INCLUDING EMERGENCY POWER SYSTEMS PER SECTION 1011.6.3.
3. SHEET 1.1; CODE REVIEW CHECKLIST: VERIFY THE OCCUPANT LOAD AS INDICATED FOR THE ASSEMBLY AREA.
4. SHEET 1.1; CODE REVIEW CHECKLIST: INDICATE ON THE PLAN THE SPECIFIC AUTOMATIC SPRINKLER SYSTEM REQUIRED PER THE IBC SECTION 903.3.1.
5. SHEET 1.1; BUILDING PLAN: INDICATE ON THE PLAN THE LOCATION AND SIZE OF PORTABLE FIRE EXTINGUISHERS PER THE IBC SECTION 906.
6. SHEET 1.1; CODE REVIEW CHECKLIST: INDICATE ON THE PLAN THE FIRE ALARM AND DETECTION SYSTEM REQUIRED PER THE IBC SECTION 907.
7. SHEET 1.1; BUILDING PLAN: REVERSE THE SWING DIRECTION ON THE DOUBLE DOOR EXIT ON THE EAST SIDE OF THE SANCTUARY.
8. SHEET 1.1; BUILDING PLAN: INDICATE ON THE PLAN THE REQUIRED AISLE WIDTHS REQUIRED FOR EGRESS PER THE IBC SECTION 1028.6.
9. SHEET 1.1; BUILDING PLAN: INDICATE ON THE PLAN THE TRAVEL DISTANCE TO AN EXIT DOOR MEETS THE REQUIREMENT OF THE IBC SECTION 1028.7, AND THE COMMON PATH OF EGRESS TRAVEL PER THE IBC SECTION 1028.8.
10. SHEET 1.1; BUILDING PLAN: INDICATE ON THE PLAN THAT THE REMAINDER OF THIS BUILDING (OTHER THAN THE SANCTUARY) IS NOT FOR CLASSROOM USE WITH THE APPROVAL OF THIS TEMPORARY C OF O.
11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/27/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change 1. PROVIDE COPIES OF THE ANNUAL FIRE SPRINKLER AND FIRE ALARM REPORTS ON RESUBMITTAL.
2. INDICATE ALL USES OF ALL SPACES ON THE PLANS.
3. CALCULATE OCCUPANT LOAD PER CHAPTER 10 AND INDICATE ON THE PLANS FOR EACH USE.
4. INDICATE THAT AN APPROVED MANUAL FIRE ALARM SYSTEM WILL BE INSTALLED BASED ON THE OCCUPANT LOAD FOR THE BUILDING EXCEEDING 300.
5. INDICATE THAT ALL EGRESS DOORS WILL BE PROVIDED WITH NO OTHER LOCK OR LATCH THEN PANIC HARDWARE.
6. PROVIDE INFORMATION REGARDING THE CHAIR SEATING. NEED TO KNOW IF THEY FOLD UP AND IF THEY CAN BE BONDED TOGETHER AS REQUIRED IN THE FIRE CODE.
7. PROVIDE INFORMATION FOR ALL DRAPERIES THAT WILL BE USED INSIDE OF THE ASSEMBLY OCCUPANCY.
8. PLEASE SUBMIT ALL THE EXITING REQUIREMENTS THAT THE BUILDING PLAN REVIEWER OUTLINED.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2015 AROMERO4 OUT TO CUSTOMER Completed