Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM00461
Parcel: 131060090

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM00461
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The hood has a total exhaust rate of 4700 CFM but the makeup air unit only supplies 3800 CFM to the room. Show how adequate make-up air is to be provided to the room so that the room pressure remains essentially neutral. Reference: Section 501.4, IMC 2012.
01/23/2015 SPOWELL1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2015 SHANAE POWELL OUT TO CUSTOMER Completed