Permit Number: T15CM00423
Parcel: 140265910

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T15CM00423
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2015 JASON GREEN ENGINEERING REVIEW Reqs Change DATE: January 22, 2015
SUBJECT: Photovoltaic System
TO: SolarCity Corporation
REVIEWERS: Jason Green, CFM


SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the Site Plan for the installation of a photovoltaic system and does not recommend approval of the Site Plan at this time.

1) Revise the site plan to accurately show the property dimensions and remove the attached duplex on the adjacent property or at a minimum dash it in with a different line weight. Refer to Zoning comments for clarity.



If you have any questions, I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services
01/28/2015 SSHIELD1 NPPO REVIEW Passed
01/28/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T15CM00423
3552 S. 5976 S. Avenida Ribero
Residential (1st Review)

TRANSMITTAL DATE: January 28, 2015

The solar plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

The structure for this site is a zero (0) lot line to the south, this plan shows the adjacent structure over the property line. Show structures correctly.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
02/03/2015 SPOWELL1 BUILDING-RESIDENTIAL REVIEW Needs Review