Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00420
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/14/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | SHEET 1 1. Change your occupancy load from 13 to 17. SHEET A1 2. For the relocated stairs please provide the following: a. Structural framing and foundation details and structural calculations. b. Large scale detail showing all accessible requirements such as dimensioning, 2 handrails, grade differences, risers and tread dimensions, landing clearances and handrail elevation with dimensions. c. Needs handrails both sides d. Land clearances non-compliant e. Confirm 3'-0" clearance for width of stair 3. Inswinging doors numbers 03 and 04 do not allow for clearances as per 2009 ICC A117.1, Section 404.2.5. a. Door 03 is not wide enough for 2-8" accessible clearances required as per Section 404.2.2. b. Why not eliminate this door. 4. New toilet room is non-compliant: a. Needs toilet clearance as per Section 604.3 b. Needs 5'-0" floor clearance turn around c. No Grab Bars d. Provide large scale details and elevations showing all accessible requirements such as dimensioning, accessories, fixtures, grad bars, heights, and signage. 5. Provide structutral calculations for the foundation and structural framing plans. END OF REVIEW |
| 04/20/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the meaning of the note on sheet A6 that states, "All mechanical, duct material, size and layout shall comply with Chapters 12 - 24 of 2012 IBC." Reference: Section 107.2.1, IBC 2012. 2. Remove all notes that refer to the IRC (e.g. Section R303.3, IRC 2012 is not applicable; the International Mechanical Code is the controlling code.) 3. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code (i.e. provide a COMcheck analysis of the envelope addition). Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012. 4. Provide NFRC fenestration product ratings for the U-factor and the SHGC values for the doors and windows on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Factory-manufactured windows are required to have certificates attesting to their compliance to NFRC Standards 100 and 200 and can be provided by the manufacturer or found at www.nfrc.org. Reference: Section C303.1.3, IECC 2012. 5. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012. 6. No exhaust fan is shown in the restroom; provide the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restroom will be exhausted during occupied hours. Reference: Section 403.2.1 (4), IMC 2012. 7. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012. |
| 04/20/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The International Plumbing Code, 2012, is the controlling code for this structure, not the International Residential Code (changing "IRC" to "IBC" in the notes does not correct the issue). Reference: Section 101.2, IPC 2012. 2. Show the location of the reduced pressure backflow assembly on the drawings; indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf 3. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy. 4. Provide fixture descriptions for all plumbing fixtures. Reference: Section 402, IPC 2012 and Section 107.2.1, IBC 2012. 5. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). 6. Provide an automatic faucet for the new lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. 7. Provide tempered water for the lavatory using a device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 8. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference: Section 107.2.1, IBC 2012. 9. Section 604.1, IPC 2012 allows water distribution systems to be designed using accepted engineering methods. Provide the source of the method used to determine the water demand and size the water distribution system. 10. Verify the pressure drop at the water meter, the water pressure range, and the static lift for the water supply. Correct the arithmetic used to calculate the pressure available for friction. 11. Coordinate the waste and vent riser diagram with the plumbing floor plan. Reference: Section 107.2.1, IBC 2012. |
| 04/20/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify the size of the existing water meter and provide its serial number. Verify the size (and existence) of the backflow preventer. The plumbing plan indicates that there is a 1" water meter with a 2" reduced pressure backflow preventer but the site plan calls out an existing ¾" meter with no backflow preventer. |
| 04/20/2015 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: 529 N. 6ht Avenue T15CM00420 Building Plan (1st Review) TRANSMITTAL DATE: April 20, 2015 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plans and they appear to match the proposed development package. Zoning cannot approve the building plans until development package, DP15-0010, has been approved. 3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 04/23/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide the following information: #1. Compliance with IECC for lighing, Tucson Outdoor Lighting Code. Ref: IBC sec. 107.2.1, IECC sec C405 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/28/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |