Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T15CM00378
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/02/2015 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | 1. Please change plans to indicate the proposed locations of portable fire extinguishers. 2. Please indicate on the plans that a manual fire alarm system will be installed per 1103.7.6 as the Fire Code Official is requiring these buildings to comply with the 2012 IFC Chapter 11. |
| 04/13/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/16/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. With regard to EF-E and EF-F, complete recirculation of ventilation air from toilet rooms is prohibited (e.g. when the occupancy sensor turns off the exhaust fan and the supply air continues to enter the room). Similarly, the restroom supplied by HP-2, EF-G is now controlled by a local switch (i.e. it operates intermittently) and the ventilation calculations indicate continuous operation. Reference: Section 403.2.1 (4), IMC 2012. [Initial comment: The ventilation calculations indicate that the restroom exhaust fans will be operating continuously during occupied hours (50 CFM per fixture instead of 70 CFM for intermittent operation), the exhaust fan schedule shows the fans controlled by a wall switch, and the electrical plans show all of the fans controlled by occupancy sensors. Clarify the operating parameters for the exhaust fans. Reference: Section 403.2.1 (4), IMC 2012.] 2. If the kitchen has been eliminated from the recreation building, shouldn't someone tell the architect? See sheet A6.1. [Initial comment: Show how adequate exhaust for the kitchen will be achieved without circulating air from the kitchen through the rest of the building and then to the restroom exhaust fans. Reference: Section 403.2.1 (3) and footnote b, Table 403.3, IMC 2012.] |
| 04/16/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |