Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM00378
Parcel: 11202005A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00378
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change 1. PLEASE INDICATE THE LEVEL OF ALTERATION PER THE IEBC CHAPTER 5 FOR THE SCOPE OF WORK AND IF THE ALTERNATE BID SCOPE IS COMPLETED.
2. PLEASE INDICATE ALL BUILDINGS THAT HAVE EXISTING FIRE ALARM OR FIRE SPRINKLER SYSTEMS AND WHICH BUILDINGS WILL COMPLY WITH CHAPTER 11 OF THE IFC FOR THE INSTALLATION OF MANUAL FIRE ALARM SYSTEMS PER 1103.7.6 AND CARBON MONOXIDE ALARMS PER 1103.9.
3.PLEASE INDICATE THE EXISTING LOCATION OF FIRE EXTINGUISHERS AND THE LOCATION OF ANY PROPOSED FIRE EXTINGUISHERS
02/18/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A6.1; ROOM FINISH SCHEDULE/MATERIAL LEGEND: THE ROOM FINISH SCHEDULE INDICATES WALLS IN THE MEN'S ROOM, WOMEN'S ROOM, AND THE TOILET REQUIRE A CT FINISH. THESE IS NO CT LISTED IN THE MATERIAL LEGEND. PLEASE PROVIDE.
2. SHEET A6.1; FLOOR PLAN: IN THE NEW MEN'S AND WOMEN'S RESTROOMS, THE INTERIOR WALLS ARE DRAWN AS EXISTING WALLS ACCORDING TO THE LEGEND. PLEASE REVISE.
3. SHEET A6.1; INTERIOR ELEVATION 1: A NOTE ON THE ELEVATION INDICATES A 48" HIGH C.T. WAINSCOT, WHILE THE ROOM FINISH SCHEDULE FOR THE THREE TOILETS INDICATES (IN THE REMARKS) A FLOOR TO CEILING C.T. WAINSCOT. PLEASE COORDINATE.
4. SHEET A6.2; EAST ELEVATION: THERE IS AN EXISTING OPENING NOT SHOWN ON THIS ELEVATION THAT IS BEING INFILLED AND WILL REQUIRE NEW STUCCO. PLEASE REVISE THE ELEVATION.
5. SHEET S2.7 (FOUNDATION PLAN); SHEET S3.0 (DETAIL 106): DETAIL 106 INDICATES A NEW FOOTING AT THE NEW STEEL COLUMN (NOTE 6), WHILE THE PLAN INDICATES A NEW SLAB CUT (KEYNOTE 3), BUT DOES NOT CALL OUT A NEW FOOTING. PLEASE CLARIFY.
6. SHEET S2.7.1 (ROOF FRAMING PLAN); SHEET S4.1 (DETAIL 216): DOES THE NEW STEEL COLUMN EXTEND TO THE EXISTING WOOD RIDGE BEAM, OR DOES IT STOP AT THE NEW LINTEL BEAM? DETAIL 216 INDICATES THE COLUMN EXTENDING PAST THE NEW LINTEL BEAM, WHILE DETAIL 228 INDICATES A 2X4 WOOD STUD WALL ABOVE THE LINTEL. PLEASE CLARIFY.
7. SHEET S2.7.1 (ROOF FRAMING PLAN); SHEET S4.1 (DETAIL 214): THE DETAIL INDICATES A 1/2" X 10" X 0'-10" STEEL BASEPLATE, WHILE PLAN KEYNOTE 2 INDICATES A 1/2" X 12" X 1'-0" SQUARE BASEPLATE. PLEASE COORDINATE.
8. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/24/2015 ROBERT SHERRY WATER REVIEW Completed
02/24/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the building. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
2. The ventilation calculations indicate that the restroom exhaust fans will be operating continuously during occupied hours (50 CFM per fixture instead of 70 CFM for intermittent operation), the exhaust fan schedule shows the fans controlled by a wall switch, and the electrical plans show all of the fans controlled by occupancy sensors. Clarify the operating parameters for the exhaust fans. Reference: Section 403.2.1 (4), IMC 2012.
3. Show how adequate exhaust for the kitchen will be achieved without circulating air from the kitchen through the rest of the building and then to the restroom exhaust fans. Reference: Section 403.2.1 (3) and footnote b, Table 403.3, IMC 2012.
02/25/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/03/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please verify egress lighting is in compliance with IBC 1006.1 .Also in compliance with Tucson Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/31/2015 SHANAE POWELL OUT TO CUSTOMER Completed
03/31/2015 SHANAE POWELL REJECT SHELF Completed