Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00375
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/09/2015 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | 1. PLEASE INDICATE THE LEVEL OF ALTERATION PER THE IEBC CHAPTER 5 FOR THE SCOPE OF WORK AND IF THE ALTERNATE BID SCOPE IS COMPLETED. 2. PLEASE INDICATE ALL BUILDINGS THAT HAVE EXISTING FIRE ALARM OR FIRE SPRINKLER SYSTEMS AND WHICH BUILDINGS WILL COMPLY WITH CHAPTER 11 OF THE IFC FOR THE INSTALLATION OF MANUAL FIRE ALARM SYSTEMS PER 1103.7.6 AND CARBON MONOXIDE ALARMS PER 1103.9. 3.PLEASE INDICATE THE EXISTING LOCATION OF FIRE EXTINGUISHERS AND THE LOCATION OF ANY PROPOSED FIRE EXTINGUISHERS |
02/18/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET T1; EXISTING UNIT MIX TABLE: THE TABLE INDICATES BUILDING F HAS 27 UNITS. THE 2012 INTERNATIONAL EXISTING BUILDING CODE, SECTION 410.8.7, INDICATES THE SLEEPING UNITS OF AN R-2 OCCUPANCY MUST MEET THE REQUIREMENTS OF SECTION 1107 OF THE INTERNATIONAL BUILDING CODE. TYPE A UNITS MUST FOLLOW SECTION 1107.6.2.1.1, AND TYPE B UNITS MUST FOLLOW SECTION 1107.6.2.1.2. IT DID NOT APPEAR THESE REQUIREMENTS WERE MET ON THE DRAWINGS. PLEASE REVISE THE DRAWINGS AS REQUIRED, AND LIST THE PERTINENT IBC SECTIONS FOR THESE REVISIONS ON THE DRAWINGS. 2. SHEETS U1 AND U2; FLOOR PLAN: PLEASE VERIFY THE REQUIREMENTS OF SECTION 420 OF THE IBC ARE MET IN THE EXISTING STRUCTURE. 3. SHEETS U1 AND U2; FLOOR PLAN: PLEASE VERIFY THE REQUIREMENTS OF SECTION 403 OF THE IEBC ARE MET FOR THE ALTERATIONS TO THE EXISTING STRUCTURE. 4. SHEETS U1 AND U2; FLOOR PLAN: WHERE ARE THE SIZE AND SPACING OF THE STUDS IN THE NEW WALLS INDICATED ON THE PLANS? PLEASE VERIFY. 5. SHEET A4 (BUILDING PLAN); SHEET A5.1 (ELEVATION 2): THE PLAN REFERENCES ELEVATION 2/A5.1 ON BUILDING F (WEST WALL), BUT ELEVATION 2/A5.1 IS THE ELEVATION FOR BUILDING G (SOUTH WALL). PLEASE REVISE. 6. GENERAL: PLEASE REVIEW CHAPTER 5 OF THE IEBC TO DETERMINE THE LEVEL OF ALTERATION PER SECTIONS 503 THROUGH 505. PROVIDE AN ANALYSIS ON THE PLANS USING CHAPTERS 7, 8, AND 9 FOR THE EXTENT OF THE ALTERATIONS REQUIRED. 7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
02/24/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
02/24/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide thermal load and HVAC equipment-sizing calculations to confirm the specified heat pumps for each apartment type. Reference: Section R403.6, IECC 2012. |
02/25/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
03/03/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following items for code compliance. #1. Verify egress lighting ( not shown on plans ) complies with IBC 1006. #2. Apartment units to comply with NEC, IBC, for the following: (a). Receptacle placement on electrical floor plans complies with 12 foot spacing as per Key Note #3 on plan sheet E2.0 and NEC 210.52 A 1. (b). AFCI protection as required per NEC 210.12 A and B. (c). Convenience receptacle required in balconies per NEC 210.53 E3. (d).Panel schedules ( plan sheet E6.3 ) are to general. Please identify circuit breaker designation to a specific unit or building, not just tenant panels. NEC 408.4 (e). Luminaires in bathrooms not shown on plans, existing or new? (f). Smoke detectors as required by IBC sec.907 not shown. #3. Plan sheet E6.3 not shown on cover sheet. #4. Please show compliance with the Tucson Outdoor Lighting Code. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/31/2015 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
03/31/2015 | SHANAE POWELL | REJECT SHELF | Completed |