Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM00371
Parcel: 11202005A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00371
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change 1. PLEASE INDICATE THE LEVEL OF ALTERATION PER THE IEBC CHAPTER 5 FOR THE SCOPE OF WORK AND IF THE ALTERNATE BID SCOPE IS COMPLETED.
2. PLEASE INDICATE ALL BUILDINGS THAT HAVE EXISTING FIRE ALARM OR FIRE SPRINKLER SYSTEMS AND WHICH BUILDINGS WILL COMPLY WITH CHAPTER 11 OF THE IFC FOR THE INSTALLATION OF MANUAL FIRE ALARM SYSTEMS PER 1103.7.6 AND CARBON MONOXIDE ALARMS PER 1103.9.
3.PLEASE INDICATE THE EXISTING LOCATION OF FIRE EXTINGUISHERS AND THE LOCATION OF ANY PROPOSED FIRE EXTINGUISHERS
02/18/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET U3; FLOOR PLAN: PLEASE VERIFY THE REQUIREMENTS OF SECTION 420 OF THE IBC ARE MET IN THE EXISTING STRUCTURE.
2. SHEET U3; FLOOR PLAN: PLEASE VERIFY THE REQUIREMENTS OF SECTION 403 OF THE IEBC ARE MET FOR THE ALTERATIONS TO THE EXISTING STRUCTURE.
3. SHEET U3; FLOOR PLAN: WHERE ARE THE SIZE AND SPACING OF THE STUDS IN THE NEW WALLS INDICATED ON THE PLANS? PLEASE VERIFY.
4. SHEET S2.1 (SECOND FLOOR PLAN); SHEET S4.1 (DETAIL 214): THE DETAIL INDICATES A 1/2" X 10" X 0'-10" STEEL BASEPLATE, WHILE PLAN KEYNOTE 3 INDICATES A 1/2" X 12" X 1'-0" SQUARE BASEPLATE. PLEASE COORDINATE.
5. SHEET S2.1 (FIRST FLOOR PLAN BUILDING A); SHEET S3.0 (DETAIL 104): THE PLAN INDICATES A 5'-6" X 2'-6" X 12" THICK FOOTING AT THE POST. PLEASE INDICATE ON THE DETAIL WHERE THE 12" THICKNESS OCCURS.
6. SHEET S4.1; DETAIL 215: SHOULD THE NEW JOIST (NOTE 3) BE SLOPED TO MATCH THAT SHOWN IN DETAIL 213? PLEASE CLARIFY.
7. SHEET S4.2; DETAIL 224: NOTE 4 INDICATES A NON STRUCTURAL WOOD STUD WALL. IT APPEARS TO BE SUPPORTING A STORAGE AREA (PER NOTE 12). PLEASE CLARIFY.
8. GENERAL: PLEASE REVIEW CHAPTER 5 OF THE IEBC TO DETERMINE THE LEVEL OF ALTERATION PER SECTIONS 503 THROUGH 505. PROVIDE AN ANALYSIS ON THE PLANS USING CHAPTERS 7, 8, AND 9 FOR THE EXTENT OF THE ALTERATIONS REQUIRED.
9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/24/2015 ROBERT SHERRY WATER REVIEW Completed
02/24/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/24/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide thermal load and HVAC equipment-sizing calculations to confirm the specified heat pumps for each apartment type. Reference: Section R403.6, IECC 2012.
03/03/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following items for code compliance.
#1. Verify egress lighting ( not shown on plans ) complies with IBC 1006.

#2. Apartment units to comply with NEC, IBC, for the following:
(a). Receptacle placement on electrical floor plans complies with 12 foot spacing as per Key Note #3 on plan sheet E2.0 and NEC 210.52 A 1.
(b). AFCI protection as required per NEC 210.12 A and B.
(c). Convenience receptacle required in balconies per NEC 210.53 E3.
(d). Please be more specific on one line diagram ( plan sheet E5.0 ). Which "D" panels feed buildings `A' and `B' ? IBC 107.2.1 NEC 110.3 and 408.4.
(e).Panel schedules ( plan sheet E6.3 ) are to general. Please identify circuit breaker designation to a specific unit or building, not just tenant panels. NEC 408.4
(f). Luminaires in bathrooms not shown on plans, existing or new?
(g). Smoke detectors as required by IBC sec.907 not shown.
#3. Plan sheet E6.3 not shown on cover sheet.

#4. Please show compliance with the Tucson Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/31/2015 SHANAE POWELL OUT TO CUSTOMER Completed
03/31/2015 SHANAE POWELL REJECT SHELF Completed