Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T15CM00370
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/22/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Completed | |
07/22/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
07/22/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The capacity of heat pump HP-3 has increased. Provide heating and cooling load calculations that justify the capacity of the specified equipment. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. |
07/31/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/14/2015 | AROMERO4 | APPROVAL SHELF | Approved |
08/14/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |