800 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM00345
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S-1; SPECIFICATIONS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES.
2. SHEET S-1 (NOTES); DETAIL 02: THE DETAIL INDICATES A HIGH STRENGTH BOLT (A325), WHILE NOTE 2 (IN BOLTS AND FASTENERS) INDICATES 'ALL MACHINE BOLTS/SCREWS AND LAG BOLTS/SCREWS SHALL CONFORM TO ASTM A307, GRADE A'. PLEASE CLARIFY.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/18/2015 CPIERCE1 REJECT SHELF Completed