Permit Number: T15CM00336
Parcel: 10605145B

Address:
3739 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00336
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/17/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Correct the ventilation calculations; include the area outdoor airflow rate, Ra (0.12 CFM/SF), from Table 403.3, IMC 2012. [Second comment: Provide ventilation calculations per the current mechanical code; see Section 403.3, IMC 2012.] [Initial comment: Provide calculations to show that adequate ventilation is being provided. Reference: Section 403.3, IMC 2012.]
03/27/2015 AROMERO4 FIRE REVIEW Needs Review