Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00336
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/17/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/17/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Correct the ventilation calculations; include the area outdoor airflow rate, Ra (0.12 CFM/SF), from Table 403.3, IMC 2012. [Second comment: Provide ventilation calculations per the current mechanical code; see Section 403.3, IMC 2012.] [Initial comment: Provide calculations to show that adequate ventilation is being provided. Reference: Section 403.3, IMC 2012.] |
03/27/2015 | AROMERO4 | FIRE | REVIEW | Needs Review |