Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00336
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/23/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide ventilation calculations per the current mechanical code; see Section 403.3, IMC 2012. [Initial comment: Provide calculations to show that adequate ventilation is being provided. Reference: Section 403.3, IMC 2012.] |
| 02/24/2015 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | 1. THE EGRESS PLAN DOES NOT MATCH THE ELECTRICAL PLAN FOR EXIT SIGNAGE 2. NEED TO KNOW THE EXISTING EMERGENCY EGRESS LIGHTING IN THE BUILDING, DOES NOT SHOW ON ON ELECTRICAL PLANS. 3. UPDATE IFC TO 2012 ON COVER SHEET |
| 02/24/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please up date your building code references. END OF REVIEW |