Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00336
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/16/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/16/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 01/20/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/20/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide calculations to show that adequate ventilation is being provided. reference: section 403.3, IMC 2012. 2. Verify that the exhaust flow rates for the existing exhaust fans exceed the proposed supply flow rates and that the exhaust fans are running whenever supply air is delivered to the restrooms during occuppied hours. Reference: Section 403.2.1 (4), IMC 2012. |
| 01/20/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | SHEET A000 1. Life Safety Plan a. Can not exit through a warehouse. Revise exiting accordingly 2. Need to update code editions. a. Remove ADA as a code reference, insert 2012 IBC, Chapter 11 and 2009 ICC A117.1 3. Provide construction type. |
| 01/20/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 01/20/2015 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | NEED TO UPDATE CODE EDITIONS AND INDICATE THAT THE DENSISTY OF THE FIRE SPRINKLER SYSTEM WILL NEED TO MEET NEW STORAGE REQUIREMENTS (MATTRESSES)-NOTE COULD BE ADDED ON A001 #47 |
| 01/21/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/23/2015 | AROMERO4 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 02/23/2015 | AROMERO4 | WWM | REVIEW | Completed |