Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00277
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/15/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 01/15/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 01/15/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide ASSE 1070 rated mixing valve for the restroom lavatories. 2. Provide structural calculations for the water heater support. |
| 01/15/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/15/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | SHEET A2 1. Delete the closer from door 109 or provide proper accessible clearances as per ICC A117.1, Section 404.2.3.2. 2. Change elevation reference from 104C to 101C. 3. Provide wall mounted water heater and support partition structural calculations. SHEET A0 4. Provide automatic sprinklers to building typer B/AS 5. Rework occupancy load to 1/100 = 25 occupants |
| 01/15/2015 | RSHERRY1 | WWM | REVIEW | Passed | No water meter size change. |
| 01/15/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 01/15/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 01/15/2015 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 01/21/2015 | SPOWELL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |