Permit Number: T15CM00277
Parcel: 14118620A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00277
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2015 DAVID RIVERA ZONING REVIEW Approved
01/15/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/15/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide ASSE 1070 rated mixing valve for the restroom lavatories.
2. Provide structural calculations for the water heater support.
01/15/2015 ROBERT SHERRY WATER REVIEW Completed
01/15/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET A2
1. Delete the closer from door 109 or provide proper accessible clearances as per ICC A117.1, Section 404.2.3.2.
2. Change elevation reference from 104C to 101C.
3. Provide wall mounted water heater and support partition structural calculations.
SHEET A0
4. Provide automatic sprinklers to building typer B/AS
5. Rework occupancy load to 1/100 = 25 occupants
01/15/2015 RSHERRY1 WWM REVIEW Passed No water meter size change.
01/15/2015 KEN BROUILLETTE FIRE REVIEW Approved
01/15/2015 JASON GREEN ENGINEERING REVIEW Approved
01/15/2015 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
01/21/2015 SPOWELL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review