Permit Number: T15CM00250
Parcel: 14029043B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T15CM00250
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/11/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S2.01 (FOOTING SCHEDULE); STRUCTURAL CALCULATIONS: THE CALCULATIONS FOR COLUMN FOOTING F18.5 INDICATES A 18'-6" X 6'-0" X 30" FOOTING, WHILE THE SCHEDULE ON SHEET S2.01 INDICATES A 18'-6" X 5'-9 X 2'-6 FOOTING. PLEASE CLARIFY.
2. GENERAL: PLEASE PROVIDE A WRITTEN RESPONSE TO THE COMMENT.
08/14/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1. Please indicate feeder conductor material (copper or aluminum ), insulation types for all feeders shown on the one line diagram plan sheet E4.1.
Please verify that the feeder conductor sizes and types are sufficient for loads and overcurrent protection as shown for panels 'PPA' and 'PPB'. Plan Sheet E4.1, E5.1, E5.2.
Ref; IBC sec. 107.2.1, NEC art. 240, 310.15 B 16,

Final Status

Task End Date Reviewer's Name Type of Review Description
09/03/2015 EGALLET1 APPROVAL SHELF Completed
09/03/2015 EGALLET1 OUT TO CUSTOMER Completed
09/03/2015 EGALLET1 REJECT SHELF Completed