Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM00250
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/15/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/23/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET AE-101; FLOOR PLAN (KEYED NOTE 13): NO DETAIL OR NOTE WAS FOUND IN THE PLANS CONCERNING THE FIRE EXTINGUISHER CABINET IN THE RATED WALL (TWO LOCATIONS ON THE PLAN). HOW IS THE WALL RATING CONTINUITY PROTECTED AT THESE PENETRATIONS? ADDRESS ANY OTHER PENETRATIONS IN THOSE RATED WALLS AND INDICATE HOW THE WALL RATING IS PRESERVED. PLEASE CLARIFY ON THE DRAWINGS. 2. SHEET AE-101 (FLOOR PLAN); SHEET AE-601 (DOOR SCHEDULE): PLEASE VERIFY THE GLAZING IN THE DOORS AND WALLS IN THE RATED WALLS MEET THE REQUIREMENTS FOR THAT ASSEMBLY. DOORS 110, 126B, 129A, 129B, AND 144A DO NOT INDICATE GLASS IN THE DOORS, BUT INDICATE FP-GL-1 IN THE 'COMMENTS'. 3. SHEET AE-101 (FLOOR PLAN); STRUCTURAL CALCULATIONS AND DRAWINGS: KEYED NOTE 4 ON AE-101 INDICATES A BRIDGE CRANE, BUT THE STRUCTURAL CALCULATIONS AND THE STRUCTURAL DRAWINGS DO NOT INDICATE THAT CRANE LOADING/CALCULATION OR CRANE SUPPORT DETAILS. PLEASE VERIFY. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |