Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/23/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET AE-101; FLOOR PLAN (KEYED NOTE 13): NO DETAIL OR NOTE WAS FOUND IN THE PLANS CONCERNING THE FIRE EXTINGUISHER CABINET IN THE RATED WALL (TWO LOCATIONS ON THE PLAN). HOW IS THE WALL RATING CONTINUITY PROTECTED AT THESE PENETRATIONS? ADDRESS ANY OTHER PENETRATIONS IN THOSE RATED WALLS AND INDICATE HOW THE WALL RATING IS PRESERVED. PLEASE CLARIFY ON THE DRAWINGS.
2. SHEET AE-101 (FLOOR PLAN); SHEET AE-601 (DOOR SCHEDULE): PLEASE VERIFY THE GLAZING IN THE DOORS AND WALLS IN THE RATED WALLS MEET THE REQUIREMENTS FOR THAT ASSEMBLY. DOORS 110, 126B, 129A, 129B, AND 144A DO NOT INDICATE GLASS IN THE DOORS, BUT INDICATE FP-GL-1 IN THE 'COMMENTS'.
3. SHEET AE-101 (FLOOR PLAN); STRUCTURAL CALCULATIONS AND DRAWINGS: KEYED NOTE 4 ON AE-101 INDICATES A BRIDGE CRANE, BUT THE STRUCTURAL CALCULATIONS AND THE STRUCTURAL DRAWINGS DO NOT INDICATE THAT CRANE LOADING/CALCULATION OR CRANE SUPPORT DETAILS. PLEASE VERIFY.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.