Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM00250
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/23/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | The calculations as per Section 508.4.2 are not summarized as required. When added, the sum of all the area ratios is 1.19391 which is grater than 1 which is not in code compliance for allowable building areas and separations. a. All of the areas listed must be separated which some are not: assembly and storage. Reevaluate your building classification type and see if it will meet the requirements of a IIIB classification. This will allow increased sizes. END OF REVIEW |
| 04/24/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/27/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Upon the third review, it is noted that the areas classified "H3"( HIGH HAZARD) by the Architect of record remain classified as such, and the quantities of hazardous substances or materials to be dispersed, handled, or stored is unknown, with exception of the photograph that shows trays full of little bottles. It seems only logical that NEC art. 500.5B2 would apply per description, for the wiring methods required in these areas( also see Informational Note #1 and #2) . |