Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM00250
Parcel: 14029043B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM00250
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change The calculations as per Section 508.4.2 are not summarized as required. When added, the sum of all the area ratios is 1.19391 which is grater than 1 which is not in code compliance for allowable building areas and separations.
a. All of the areas listed must be separated which some are not: assembly and storage.

Reevaluate your building classification type and see if it will meet the requirements of a IIIB classification. This will allow increased sizes.
END OF REVIEW
04/24/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/27/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Upon the third review, it is noted that the areas classified "H3"( HIGH HAZARD) by the Architect of record remain classified as such, and the quantities of hazardous substances or materials to be dispersed, handled, or stored is unknown, with exception of the photograph that shows trays full of little bottles. It seems only logical that NEC art. 500.5B2 would apply per description, for the wiring methods required in these areas( also see Informational Note #1 and #2) .