Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM00250
Parcel: 14029043B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM00250
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change 1. As per previous comment 13, please show all dimensions for accessible requirements. The dimensions shown are not dimensions for accessible clearances. Please reference the 2009 ICC A117.1, Section 603 Toilet and Bathing Rooms. Specifically, please note Section 604.3 which calls for a toilet clearance of 5'-0" wide and 4'-8" deep with no other fixture encroachment into this area. Please redesign your toilet room to accommodate these requirements and other dimensions as required.
a. This requirement also applies to detail A1/AE-402
2. For separated uses, please provide on the drawings the calculation required by section 508.4.2 to show that the areas of the separated uses do not exceed 1.
END OF REVIEW
03/24/2015 KEN BROUILLETTE FIRE REVIEW Approved
03/25/2015 ROBERT SHERRY WATER REVIEW Completed
03/25/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/31/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Envelope assemblies that have not been selected from the assembly menus of COMcheck (e.g. other roof) require supporting documentation to show how the proposed U-factors have been calculated. The exterior walls depicted in details A1, A2, and A3/AE-302 do not indicate the presence of any continuous insulation; clarify this discrepancy. See footnote (b) in Section 3; if the U-factors and SHGC values for the proposed fenestration components (e.g. doors and windows) are not certified by NFRC and have no supporting documentation, the default values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012 must be used in COMcheck. [Initial comment: The plans appear to show that the existing building will have an increase in energy use due to this change in occupancy. The occupancy change will require the building (i.e. the envelope, mechanical systems, lighting, and service water heating) to be brought into compliance with the current code. Reference: Section C101.4.4, IECC 2012.]
2. The return air from the office areas appears to pass through the fire partition surrounding room 110; how is this accomplished? [Initial comment: Clarify how the penetration of the fire barrier between the business and H-3 occupancy by the supply duct and the air transfers for the return air plenum comply with the requirements of Section 607, IMC 2012.]
04/01/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1. Upon second electrical plan review it was revealed to the Electrical Plan Reviewer that there are areas classified as "H3" ( Use of Flammable or Combustible materials) per the architectural drawings. These areas are not shown on the electrical floor plans or notes. Please address this and classify these areas per the NEC as necessary for the application of the correct wiring methods to ensure a safe and code compliant electrical installation in these areas .
#2. Please provide compliance with section 402.1 ( color temperature ) for the outside lighting.
Reference: IBC sections, 107.2.1 , 307.5 , NEC articles 100 -thru- 506.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/10/2015 SHANAE POWELL OUT TO CUSTOMER Completed
04/10/2015 SHANAE POWELL REJECT SHELF Completed