Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00249
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/14/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/14/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 01/14/2015 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 01/14/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1; FLOOR PLAN KEYNOTES: NOTES 5, 12, AND 13 WERE NOT LOCATED ON THE PLANS. VERIFY. 2. SHEET A1; T.I. CODE REVIEW: THE EXIT WIDTH CALCULATION IS BASED ON 6 OCCUPANTS, WHILE THE OCCUPANT LOAD CALCULATION INDICATES 50 OCCUPANTS. COORDINATE. 3. SHEET A1; FLOOR PLAN KEYNOTE 14: PROVIDE A DETAIL ON THE DRAWINGS FOR THE WATER HEATER SUPPORT. 4. SHEET A1; REFLECTED CEILING PLAN KEYNOTES: WHERE ARE THESE KEYNOTES LOCATED ON THIS DRAWING? VERIFY. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/14/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 01/16/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 01/16/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the minimum plumbing fixtures (e.g. drinking fountain) per Table 2902.1, IBC 2012 |
| 01/16/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/16/2015 | AROMERO4 | FIRE | REVIEW | Needs Review | |
| 01/16/2015 | RSHERRY1 | WWM | REVIEW | Passed | No water meter size change. |