Permit Number: T15CM00243
Parcel: 10509550A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00243
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2015 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
01/15/2015 ROBERT SHERRY WATER REVIEW Completed
01/15/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a natural gas piping design, including the piping layout on a floor plan and a natural gas schematic showing the sizes, loads and developed lengths of the piping. Reference: Section 107.2.1, IBC 2012.
01/15/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
2. Show that the proposed rooftop units meet the requirements of Sections C403.2.2, C403.2.3, C403.2, and C403.3 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
01/21/2015 MARTIN BROWN FIRE REVIEW Approved
01/23/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved