Permit Number: T15CM00163
Parcel: 105102420

Address:
455 E WETMORE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM00163
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/28/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed; provide a written response to the comment. [Initial comment: Clarify the specifications of AHU-1 with regard to energy use and air flow balancing. The submitted COMcheck Mechanical Compliance Certificate indicates that the unit is for heating only but the drawing shows condensate drains for the unit and the note H on the Air Handling Unit Schedule states that the unit has an EER of 14.3. The schedule shows no outside air for the unit but note C of the schedule states that "Outside air is conditioned through the air handling unit for the sales floor area in accordance with ASHRAE 62-2007." Reference: Sections C303.1 and C403.1, IECC 2012.]
2. Comment not addressed; provide a written response to the comment. [Initial comment: If AHU-1 is not introducing outside air into the sales floor, show how adequate outside air is to be supplied from the remaining rooftop units after RTU-25 has been removed. Reference: Section 403.3, IMC 2012.]
04/29/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved