Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM00163
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/13/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
01/22/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Needs Review | ARCHITECT HAS RAMP CHANGES TO BE ADDED FOR ADDITIONAL REVIEW. |
01/30/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/30/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
02/02/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the specifications of AHU-1 with regard to energy use and air flow balancing. The submitted COMcheck Mechanical Compliance Certificate indicates that the unit is for heating only but the drawing shows condensate drains for the unit and the note H on the Air Handling Unit Schedule states that the unit has an EER of 14.3. The schedule shows no outside air for the unit but note C of the schedule states that "Outside air is conditioned through the air handling unit for the sales floor area in accordance with ASHRAE 62-2007." Reference: Sections C303.1 and C403.1, IECC 2012. 2. If AHU-1 is not introducing outside air into the sales floor, show how adequate outside air is to be supplied from the remaining rooftop units after RTU-25 has been removed. Reference: Section 403.3, IMC 2012. |
02/04/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide 2012 IECC complience. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/14/2015 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
04/14/2015 | CPIERCE1 | REJECT SHELF | Completed |