Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM00163
Parcel: 105102420

Address:
455 E WETMORE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00163
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2015 KEN BROUILLETTE FIRE REVIEW Approved
01/22/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Needs Review ARCHITECT HAS RAMP CHANGES TO BE ADDED FOR ADDITIONAL REVIEW.
01/30/2015 ROBERT SHERRY WATER REVIEW Completed
01/30/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the specifications of AHU-1 with regard to energy use and air flow balancing. The submitted COMcheck Mechanical Compliance Certificate indicates that the unit is for heating only but the drawing shows condensate drains for the unit and the note H on the Air Handling Unit Schedule states that the unit has an EER of 14.3. The schedule shows no outside air for the unit but note C of the schedule states that "Outside air is conditioned through the air handling unit for the sales floor area in accordance with ASHRAE 62-2007." Reference: Sections C303.1 and C403.1, IECC 2012.
2. If AHU-1 is not introducing outside air into the sales floor, show how adequate outside air is to be supplied from the remaining rooftop units after RTU-25 has been removed. Reference: Section 403.3, IMC 2012.
02/04/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide 2012 IECC complience.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2015 SHANAE POWELL OUT TO CUSTOMER Completed
04/14/2015 CPIERCE1 REJECT SHELF Completed