Permit Number: T15CM00155
Parcel: 12710017D

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T15CM00155
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change As per note #7 on revised plan sheet E2, tap for new feeder cannot be on the line side of the service disconnecting means as this would not allow for overcurrent protection and be in violation of NEC art. 240, 408.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2015 AROMERO4 APPROVAL SHELF Completed
05/13/2015 AROMERO4 OUT TO CUSTOMER Completed