Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T15CM00155
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | As per note #7 on revised plan sheet E2, tap for new feeder cannot be on the line side of the service disconnecting means as this would not allow for overcurrent protection and be in violation of NEC art. 240, 408. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/13/2015 | AROMERO4 | APPROVAL SHELF | Completed |
| 05/13/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |