Permit Number: T15CM00132
Parcel: 13821030F

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T15CM00132
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2015 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T15CM00132

1. Electrical plan:
a. Provide the location and protection for the gel cell batteries.
b. Provide wiring diagram with conductor and conduit sizes.
c. Show a lighting control device.

2. City of Tucson Outdoor Lighting Code (Ord #10963) compliance: Compare total fixture output to the budget based on property size and zone location (Table 401.1).
a. Include all exterior (existing) fixtures within the property lines. The ordinance requires identification of each fixture type (both Full-Cut-Off and un-shielded); and fixture output based on a typical lamp lumen output at the maximum fixture wattage rating. Include landscape fixtures in the existing total and determine the qualified option limit.
b. The rated color temperature of proposed fixtures shall not exceed 3500K, Section 402. The provided manufacturer spec sheet shows a non-conformant color temperature rating over 3500K.

3. Update the Sol manufacturer spec sheet with appropriate project name and quanity.

Ken Van Karsen
Electrical Plan Review
PDSD, City of Tucson