Review Details: WALK THRU - COMM
Permit Number - T15CM00132
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2015 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T15CM00132 1. Electrical plan: a. Provide the location and protection for the gel cell batteries. b. Provide wiring diagram with conductor and conduit sizes. c. Show a lighting control device. 2. City of Tucson Outdoor Lighting Code (Ord #10963) compliance: Compare total fixture output to the budget based on property size and zone location (Table 401.1). a. Include all exterior (existing) fixtures within the property lines. The ordinance requires identification of each fixture type (both Full-Cut-Off and un-shielded); and fixture output based on a typical lamp lumen output at the maximum fixture wattage rating. Include landscape fixtures in the existing total and determine the qualified option limit. b. The rated color temperature of proposed fixtures shall not exceed 3500K, Section 402. The provided manufacturer spec sheet shows a non-conformant color temperature rating over 3500K. 3. Update the Sol manufacturer spec sheet with appropriate project name and quanity. Ken Van Karsen Electrical Plan Review PDSD, City of Tucson 520-837-4912 Kenneth.VanKarsen@tucsonaz.gov |