Permit Number: T15CM00077
Parcel: 117042490

Address:
510 N 7TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00077
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S1 (FOUNDATION PLAN KEYNOTES); STRUCTURAL CALCULATIONS (SHEET 10): THE CALCULATIONS INDICATE 600 AWC X 20 GA.METAL STUDS AT 16" OC AT INTERIOR WALL STUDS FOR WALLS GREATER THAN 12' IN HEIGHT (UP TO 14' HEIGHT). IT APPEARS THE INTERIOR DEMISING WALL STUDS EXCEED THE 12' HEIGHT, BUT THE FOUNDATION KEYNOTE 2 INDICATES ONLY 4" METAL STUDS. CLARIFY.
2. GENERAL: VERIFY ON THE DRAWINGS THAT THE MEZZANINES MEET THE REQUIREMENTS OF THE IBC SECTION 505.
3. SHEET G1; BUILDING CODE INFORMATION: THE OCCUPANCY TYPE IS LISTED AS B, WHILE THE PLAN ON SHEET A1 INDICATES WAREHOUSE FOR EACH SPACE. CLARIFY.
4. SHEET G1; BUILDING CODE INFORMATION: THE OCCUPANT LOADS ARE NOT REQUIRED AT THIS TIME SINCE THIS SET OF DRAWINGS IS FOR LETTER OF COMPLETION ONLY. HOW WERE THE OCCUPANT LOADS CALCULATED FOR A WAREHOUSE USE? VERIFY.
5. GENERAL: PROVIDE WRITTEN RESPONSE TO THE REVIEW COMMENT.
01/05/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/06/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/06/2015 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T15CM00077

City of Tucson Outdoor Lighting Code (Ord #10963) compliance: Compare total fixture output to the budget based on property size and zone location (Table 401.1).
a. Include all exterior (existing) fixtures within the property lines. The ordinance requires identification of each fixture type (both Full-Cut-Off and un-shielded); and fixture output based on a typical lamp lumen output at the maximum fixture wattage rating. Include landscape fixtures in the existing total and determine the qualified option limit.
b. The rated color temperature of proposed fixtures shall not exceed 3500K, Section 402. Notate plans, or provide manufacturer spec sheet with color temperature rating.

The 2012 Outdoor Lighting Code may be found on The City of Tucson Website under: www.tucsonaz.gov/pdsd; Codes, Standards, Ordinances & Guidelines; Building Codes.

Ken Van Karsen
Electrical Plan Review
PDSD, City of Tucson
520-837-4912
Kenneth.VanKarsen@tucsonaz.gov
01/06/2015 ROBERT SHERRY WATER REVIEW Reqs Change Tucson Water limits the use of 3/4" water meters to a maximum demand of 22.5 GPM. The water calculations indicate a demand of 24 GPM; approximately 29 GPM if the HVAC demand is included. Provide a letter from Tucson Water stating that they will allow the use of a 3/4" water meter with a demand of 29 GPM.
01/06/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 510 N. 7th Avenue
T14CM00077
Building Plan (1st Review)

TRANSMITTAL DATE: January 6, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plans but cannot approve until a development package for site revisions, exterior canopies, pedestrian circulation and parking restripe, has been submitted and approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/06/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/06/2015 MARTIN BROWN FIRE REVIEW Approved
01/13/2015 SPOWELL1 WWM REVIEW Needs Review
01/13/2015 SPOWELL1 ENGINEERING REVIEW Needs Review